3 phases 10KVA-200KVA High frequency Online UPS 3 phases Input and Output 380V Online ups

  • 3 phases 10KVA-200KVA High frequency Online UPS 3 phases Input and Output 380V Online ups
  • 3 phases 10KVA-200KVA High frequency Online UPS 3 phases Input and Output 380V Online ups
  • 3 phases 10KVA-200KVA High frequency Online UPS 3 phases Input and Output 380V Online ups
3 phases 10KVA-200KVA High frequency Online UPS 3 phases Input and Output 380V Online ups

Three Phases Input Three Phases Output 10KVA-200KVA Widely used in data center, network management center, Enterprise server room, telecommunication, financing, transportationGovernment, manufacturing, energy and other industries.

DT33 series, 3 phases in/3 phases out UPS is true double-conversion design, with input power factor correction (PFC), so power factor is up to 0.99. Its high-power capacity can greatly reduce its volume and floor space. With digital control, the system has high stability and the ability of self-protection and fault diagnosis. This series of UPS can better solve power supply problems such as voltage decaying, oscillation, high voltage impulse, voltage fluctuations, surges, harmonic distortion, disturbances, frequency fluctuation etc.

Features:

*True high frequency double-conversion

*Smart digital control, the system stability is higher

*With input power factor correction (PFC), power factor 0.99.

*Number of battery can be set according to users’ requirements: ±16/17/18/19/20pcs

*With parallel interface, 4pcs paralleled connection of UPS are available, and they share the same battery pack

*Charging current can be set, constant voltage charge, constant current charging and floating charge can be automatically switched.

*Using LCD and LED dual display, users can intuitively understand the working state and parameters of UPS.

*With maintenance bypass switch, UPS can be maintained without power off.

*Strong load capacity can adapt to the unbalance 3 phase loads.

*With RS-232 and SNMP (option)

*With emergency power off function (EPO), press the EPO button for emergency shutdown.

 

Photos:

 

Specifications:

Model DT33-10K DT33-20K DT33-30K DT33-40K DT33-50K DT33-60K DT33-80K DT33-100K DT33-120K DT33-160K DT33-200K
Capacity 10kVA 20kVA 30kVA 40kVA 50kVA 60kVA 80kVA 100kVA 120kVA 160kVA 200kVA
Input
Rated Voltage 380Vac (3 phase+N)
Voltage Range 304Vac ~ 478Vac (line voltage) full load; 304Vac ~ 228Vac (line voltage) load derated linearly from100% to 80%
Frequency Range 40Hz ~ 70 Hz
Power Factor ≥ 0.99@100% load;≥ 0.98@50% load
THDi <3% (100% linear load) ; <5% (100%nonlinear load)
Output
Output Voltage 380/400/415Vac (3phase+N);
Voltage Accuracy ±1%@balanced load;±5%@unbalanced
THDu ≤2% (100% linear load);≤4% (nonlinear load)
Power Factor 0.9 (1 optional)
Frequency Range ±2Hz(settable);±0.5Hz,±1Hz,±3Hz(settable) (Synchronizing Range)
Frequency Range 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Battery Mode)
Overload < 105%, long run; < 110%, 60 min; 110~125% rated load,  load 10 min; >125~150% rated load, load1 min; >150%, 200ms
Crest Factor 3:1 (maximum)
Switching Time 0 ms (Main power Battery)
1 ms (phase lock failure, <2ms interrupt occurs) (Inverter Bypass)
< 2 ms (Inverter ECO)
Efficiency
Inverter Mode ≥95%
ECO Mode ≥99%
Battery
Number Long backup 32; 30 ~ 44(±15~±22)(settable)
Standard backup (30~60)x7AH/9AH (60~80)x7AH/9AH NA
Charging Current Capacity* 15%/N/12(N=±15-22)
Charging Voltage ± 13.65Vdc * N ± 1%(N=±15-22)
Physical
Long backup Size (mm) 280 x 685 x 725 425 x 780 x 1200 600 x 800 x 1600 600 x 960
x 1600
600 x 1010
x 2000
Net Weight(kg) 45 108 230 310 360 460
Standard backup Size WxDxH(mm) 400 x 685 x 1000 425 x 780 x 1580 NA
Net Weight(kg) 62 (w/o battery) 135 (w/o battery) NA
Environment
Working Temperature 0 ~ 40°C battery life will be shorten when temperature > 25°C
Relative Humidity 0~95% no condensation
Altitude 1000 meters no derate, > 1000 meters derating 1% for every 100 meters rise
Noise ≤ 60dB (A)@ 1 meter
Management
Intelligent RS232/RS485 Support Windows® 2000/2003/XP/Vista/2008,Windows® 7/8/10,Linux and MAC
Optional SNMP / Dry contact

 

Applications

Widely used in data center, network management center,

Enterprise server room, telecommunication, financing, transportation

Government, manufacturing, energy and other industries.

 

Our Service:

1. Samples

Samples are Available for Testing and Market Test.

2. Warranty of RSUN Products
RSUN provides warranty against defects in materials and workmanship for its Uninterruptible power supply, Power inverter/chargers including inverter12v 24v 48V, Solar charge controllers (“Product”).

3. OEM Service
OEM service of RSUN is strictly based on the ISO9001 ISO14001 quality assurance system. The TOP involves the effective teamwork of departments from Sales, R&D, and Engineering, purchasing, production & QA, assuring a high quality product and prompt delivery for customers. The standardization of our quality system and the quality stability has earned us the trust of our customers for 12 years.

Get the latest price? We'll respond as soon as possible(within 12 hours)